Reports the last polled value from a Modbus input register on the slave device.
CommError is hidden by default.
Outputs
Slots
Type
Description
Out
Integer
The last polled value from the slave device, or the default value if communications with the slave device was lost.
CommError
Digital
Set to True by the block when communication with the slave device is lost.
Properties
Slots
Description
DefaultValue
The default value of the Out slot when the program starts, and the value that the block will revert to when communication is lost with the slave device.
Format
Specifies the bit format of the register on the slave device. Can be set to one of the following values:
▪SignedInt16: 16‑bit signed integer
▪UnsignedInt16: 16‑bit unsigned integer
▪SignedInt32: signed 32‑bit integer
MaxReceiveTime
The maximum time, in seconds, that can elapse with no communication to the slave device before the block assumes that communication has been lost.