NvOutputHvacStatus

Top  Previous  Next

CIRCON~1_img359

Represents an output network variable of type SNVT_hvac_status.

NvIndex is hidden by default.

The type is preset and cannot be changed. For more information about SNVT__hvac_status, see http://types.lonmark.org/.

 

Inputs



 

 

Slots

Type

Default

Description

 

Mode

Integer

0

‘mode’ field of NV

 

HeatOutputPrimary

Numeric

0

‘heat_output_primary’ field

 

HeatOutputSecondary

Numeric

0

‘heat_output_secondary’ field

 

CoolOutput

Numeric

0

‘cool_output’ field

 

EconOutput

Numeric

0

‘econ_output’ field

 

FanOutput

Numeric

0

‘fan_output’ field

 

InAlarm

Integer

0

‘in_alarm’ field

 

Outputs


 

Slots

Type

Description

 

NvIndex

Integer

The current index of the network variable.

 

Properties


 

Slots

Description

 

MinSendTime

Determines minimum period of time (in seconds) that the device waits before updating the network variable as changes in value occur.

 

MaxSendTime

Determines the maximum period of time before the associated output NVs are automatically updated.