StagesWithModulation

Top  Previous  Next

CIRCON~1_img297

Controls up to three digital stages and a single analog stage.

The number of stages in use is set by the property 'Stages'.

The single analog stage provides a modulated output for each stage. As shown in Figure 22, the analog output is the first output to stage at t0. As the input continues to increase, Out2 turns on, and Out1 turns off at t1. If the input continues to increase, Out1 will increase from 0.0% to 100% while Out2 remains on. When Out1 reaches 100% at t2, Out3 turns on. At this point Out1 goes to 0.0% and Out2 and Out3 are on. The process continues until, at t4, all three digital outputs will be on and the analog output will be at its maximum.

Figure 22: Modulated Stage OutputCIRCON~1_img298

 

Inputs

 

Slots

Type

Default

Description

 

In

Numeric

Null

The input to the block in percent (0.0 to 100.0 %).

 

Enable

Digital

True

Enables or disables the block. Disabling the block will cause the analog stages to be set to zero.

 

Outputs

 

Slots

Type

Description

 

Out1

Numeric

The single analog output to stage in percent.

 

Out2

Digital

First digital output to stage.

 

Out3

Digital

Third digital output to stage.

 

Out4

Digital

Fourth digital output to stage.

 

Properties

 

Slots

Description

 

Stages

Sets the number of outputs to stage.