The output ‘Out’ follows the input ‘In’, except that transitions from False to True are delayed for the time specified in the ‘Delay’ slot.
Inputs
|
|
|
|
|
Slots
|
Type
|
Default
|
Description
|
|
In
|
Digital
|
Null
|
The digital input for the output ‘Out’ to follow.
|
|
Enable
|
Digital
|
True
|
When True, ensures that start delay is maintained.
When False, the output ‘Out’ follows the input exactly.
|
|
Delay
|
Integer
|
60 seconds
|
The start delay in seconds, the default value is 60 seconds.
|
Outputs
|
|
|
Slots
|
Type
|
Description
|
|
Out
|
Digital
|
The output which follows the input and is modified by the Delay.
|
|